ZGB-1 corrugated flame arrester Overview:
RZGB-1
new corrugated oil tank flame arrester is China Petrochemical
Corporation Beijing Design Institute to design new products, the *
Tianjin Institute of Fire Science based on the People's Republic of
China GB5908-86 standard test qualified, The product is widely used in
oil storage tanks, is to prevent accidental fire intrusion tank, to
prevent accidents, is the ideal tank fire.
ZGB-1 Corrugated flame arrester performance and features:
?
The flame arrester has the advantages of reasonable structure, light
weight, corrosion resistance and explosion-proof performance, and can
withstand fire for 13 times in a row with a subsonic flame test.
Flame arrester easy to repair, easy to install, do not check when removing the breathing valve. Resistance to burning qualified, resistant to burning test 1 hour without tempering.
? The flame arrester core is stainless steel, corrosion-resistant and easy to clean. Shell hydraulic test qualified.
ZGB-1 corrugated flame arrester Scope:
The
flame arrester is suitable for pipes, flash point of less than 28 ℃
Class A, oil, hydrogenated liquefied and flash point of less than 60 ℃
kerosene, diesel, armor, crude oil And so on, can be used with the
respiratory valve supporting the use, but also can be used alone, within
the floating roof tank vent, gas tank on the ground floor gas tank.
Corrugated flame arrester repair and maintenance:
In
order to ensure the performance of flame arrester to achieve the
purpose of safe use, flame arresters should be regularly checked and
maintained.
? Flame arresters are inspected semi-annually to check if the fire barrier core is clogged, deformed, etched.
?
It is found that the plugged flame barrier core should be cleaned to
ensure that each hole in the core is clear and that the fire barrier
should be replaced for deformation and corrosion.
? When reinstalling the flame retardant core, ensure that the joint surface is tight and leakproof.
Wave pattern flame arrester part materials:
Body material | Carbon steel WCB, stainless steel 304,316 |
Fire retardant core material | Stainless steel explosion-proof corrugated plate |
Sealing material | Asbestos rubber, PTFE PTFE |
Ambient temperature ℃ | ≤480 ℃ |
Nominal pressure (MPa) | 0.6 ~ 5.0MPa |
Explosion-proof level | BS5501: Ⅱ A, Ⅱ B, Ⅱ C |
Corrugated flame arrester GB flange connection Dimensions: GB, JB
specification | Installation size (mm) | ||||
D2 | D | L | H | Nd | |
DN50 | ?110 | ?140 | 220 | 235 | 4 × 14 |
DN80 | ?150 | ?185 | 280 | 270 | 4 × 18 |
DN100 | ?170 | ?205 | 325 | 275 | 4 × 18 |
DN150 | ?225 | ?260 | 425 | 290 | 8 × 18 |
DN200 | ?280 | ?315 | 495 | 305 | 8 × 18 |
DN250 | ?335 | ?370 | 595 | 320 | 12 × 18 |
DN300 | ?395 | ?435 | 655 | 405 | 12 × 23 |
Corrugated flame arrester American standard flange connection Dimensions: ANSI, API, ASME for JIS standards
specification | Installation size (mm) | ||||
D2 | D | L | H | Nd | |
2" | ?120.5 | ?152 | 220 | 235 | 4 × 19 |
3 " | ?152.5 | ?190 | 280 | 270 | 4 × 19 |
4 " | ?190.5 | ?229 | 325 | 275 | 8 × 19 |
6 " | ?241.5 | ?279 | 425 | 290 | 8 × 22 |
8" | ?298.5 | ?343 | 495 | 305 | 8 × 22 |
10 " | ?362 | ?406 | 595 | 320 | 12 × 25 |
12 " | ?432 | ?483 | 655 | 405 | 12 × 25 |